The EVO-SP™ 2600 System allows operators of electric power generators to substantially reduce costs, extend emergency run-time and improve sustainability by substituting diesel fuel with lower cost, cleaner burning natural gas (NG). The EVO-SP System is comprised of proprietary and patent-pending technologies that allow the safe use of natural gas in place of diesel fuel, with substitution rates ranging from 50% to 70% of the generator’s total fuel requirement. Generators converted with the System exhibit diesel-like performance in such critical areas as load acceptance, power output, stability and efficiency. 

  • 32-bit Microcontroller with USB and CAN Communications
  • J1939 Compatible
  • Programmable Fuel Mapping
  • Remote Graphic User Interface
  • Monitors >25 Sensors 50X per Second
  • Six Channel Throttle-Body Control Output
  • 24V Input Power
  • Load Dump Overvoltage >1w00V
  • Under-Voltage Lockout <18V
  • Reverse and Double Battery Voltage Protected
  • Ambient Operating Temperature: -40°C to +105°C
  • Storage Temperature: -40°C to +125°C
  • EMC / EMI:
    • EN61000-6-2/-4
    • ISO 10605
    • ISO 11452-2,4
    • CISPR 25
  • Humidity: MIL-STD-810D, 507.2
  • Chemical Resistance: SAE J1455, 4.4.3
  • Shock: 40 Gs
  • Vibration: Random: 0.3G²/Hz, 10-2000 Hz
  • Thermal Shock: SAE J1455, 4.1.3.2
  • Ingress Protection: IP56 Per IEC 60529 SAE J1455

  • Mixer Diameter: 6” O.D. Nominal
  • Number of Mixers: 2
  • Material: 6061-T6 Aluminum
  • Fuel Supply Connection: 1.5” JIC
  • Ambient Operating Temperature: -40 to +105 °C (-40 to +221 °F)
  • Storage Temperature: -40 to +125 °C (-40 to +257 °F)
  • Humidity: US MIL-STD 810E, Method 507.3, Procedure III
  • Salt Spray: US MIL-STD 810E, Method 509.3, Procedure I
  • Shock: MS1-40G 11ms Sawtooth
  • Vibration Random: 0.3 GÇ/Hz , 10–2000 Hz (22.1Grms) 3 h/axis
  • Sine: 5 G 2.5 mm peak-to-peak, 5–2000 Hz, 3 h/axis, 90 min dwells, 1 octave/min
  • Drop: SAE J1211, Paragraph 4.8.3 (modified)
  • Thermal Shock: SAE J1455, Paragraph 4.1.3.2
  • Ingress Protection: IP56 per EN60529
  • Inlet Pressure Sealed Shaft Bearings: 2 bar (29 psi) gage
  • Standard Shaft Bearings: 0.068 bar (1 psi) gage
  • 12.1” TFT XGA LCD
  • Ingress Protection IP65 per EN60529
  • Power: 12V DC
  • Viewing Angle: -80~80 (H); -70~70 (V)
  • Active Display Area: 245.76 (H) x 184.32 (V)
  • Resolution: 1024×768
  • Ambient Operating Temperature: -20 to 60 °C (-4 to 140 °F)
  • Humidity: 10% to 95% non-condensing
  • Shock: 15G, 11 ms duration
  • Vibration: 5 Hz ~ 500 Hz / 1 Grms
  • Size: DN65
  • Ambient Operating Temperature: -15 to +60 °C (5 to 140 °F)
  • Power: 24 – 28 VDC
  • Rating: Class A Group 2, EN 161
  • Ingress Protection: IP54, IEC 529
  • Open Time: <1 Sec
  • Close Time: <1 Sec
  • Flame Detection
  • Combustible Gas Detection
  • Air-Gas Mixture Inflammable Outside Combustion Chamber
  • High Exhaust / Turbo Temperature
  • High Boost Pressure / Temperature Engine
  • Over-Speed Protection
  • High Vibration (Knock Detection)
  • Excess Diesel & Gas Flow
  • Gas Throttle Position Feedback Loop

 

Download PDF